Selecting a SystemDetermine the installation location, the load you wish to supply, and its duty cycle (what percentage of the time you wish to apply the load) following the three simple steps below:
2. Determine the load requirements for your application in Amp-hours / day. For wireless applications, determine the power of your device in amps (Cooper Crouse-Hinds wireless radio power consumption can be determined using the steps found on the following website: http://www.crouse-hinds.com/wirelessIO/Calculator/Files/CCHSolarCalc.xls 3. Select the solar kit capable of meeting or exceeding the load requirements (in Amp-hours / day) for your application. Please consult factory for higher load requirements. Amp-Hours / Day Calculation:Load requirement (Amp-hours / day) = (amps of device x duty cycle x Service Factor) x 24 hours / day |
|
| Example: 16.5 mA, continuous, temperature = 10ºC (50ºF) Load requirement = (16.5 mA x 100% x 1.2) x 24 hours / day = 475 mA-hr / day Load requirement = 0.475 Amp-hours / day |
| For more information about each kit: Solar Panels Brochure |
![]()
|
|
|
![]() |