MAXIMUM NUMBER AND SIZE OF CONDUCTORS ALLOWED IN TRADE SIZES OF CROUSE-HINDS CONDUIT BODIES
Conduit Trade Size Catalog Number Hub''
Conductor  Size  AWG,  MCM
6   4
3    2
1   1/0
2/0   3/0
4/0  250
300  350
400  500
600  700
750  900
6'' LBD014 All
.  137
116    97
72   61
 51    42
 35   28
 24   21
 19   16
 13   11
 10   
5'' LBD012 All
.   93
 79    66
49   41
 34    28
 23   19
 16   14
 12   10
  3     
      
4'' BC10, BT10, C108, C1089, E108, LL107, LL108, LL1089, LR107, LR108, LR1089,T108, T1089, TB108, X108 All
.   59
 50    42
31   26
 21    17
 14   11
 10    3
        
        
      
T107, TB107, X107 Thru
.   59
 50    42
31   26
 21    17
 14    3
        
        
        
      
Side
.   59
 50    42
31   26
 21     3
         
        
        
        
      
BLB10, BUB10,LB108, LBD10900 All
.   59
 50    42
31   26
 21    17
 14   11
 10    8
  7     3
        
      
LB107 All
.   59
 50    42
31   26
 21    17
 14   11
  3     
         
        
      
LB1089 All
.   59
 50    42
31   26
 21    17
 14   11
 10    8
  3      
        
      
LBNEC10 All
.   59
 50    42
31   26
 21    17
 14   11
 10    8
  7     6
  4     4
  3     3
3-1/2'' BC9, BT9, C98, C989, E98, LL97, LL98, LL989, T98, T989, TB98, X98 All
.   46
 38    32
24   20
 16    13
 11     9
  7    3
        
        
      
LB97 All
.   46
 38    32
24   20
 16    13
 11    9
  3      
        
        
      
T97 Thru
.   46
 38    32
24   20
 16    13
 11    3
         
        
        
      
Side
.   46
 38    32
24   20
 16     3
         
         
        
        
      
LB989 All
.   46
 38    32
24   20
 16    13
 11    9
  7    6
  3     
        
      
BLB9, BUB9, LB98, LBD9900 All
.   46
 38    32
24   20
 16    13
 11    9
  7    6
  5    3
        
      
LBNEC9 All
.   47
 39    33
25   21
 17    14
 12    10
  8    7
  6     5
  4     4
  3    
3'' C87 All
.   34
 28    24
17   14
 3      
         
        
        
        
LB87 All
.   34
 28    24
17    14
12     3
         
        
        
        
C88, C889, E88, LL87, LR87, T88, T889, TB88, X88 All
.   34
 28    24
17     14
12     10
 8      3
        
        
        
T87, X87 Thru
.   34
 28    24
 17    14
  3     
         
        
        
        
Side
.   34
 28    24
 17     3
        
         
        
        
        
BC8, LB888, LB889, LL888, LL889, LR888, LR889 All
.   34
 28    24
17     14
12     10
 8      6
 5      3
        
        
BLB8, BUB8, LBD8800 All
.   34
 28    24
17     14
12     10
 8      6
 5      3
 4      3
        
BT3 Thru
.   34
 28    24
 17    14
 12    10 
 8     6
 5     3
        
        
Side
.   34
 28    24
 17    14
 12    10
 8     6
 3     
        
        
LBNEC8 All
.   34
 28    24
17     14
12     10
 8      6
 5      4
 4      3
 3       
2-1/2'' C77 All
.   21
 18    15
11     9
 3      
         
        
        
LB77 All
.   21
 18    15
11     9
 7     3
         
        
        
T77 Thru
.   21
 18    15
11     9
 3      
         
        
        
Side
.   21
 18    15
11     3
        
         
        
        
C78, C789, E78, LL777, LR777, T78, T789, TB78, X78 All
.   21
 18    15
11     9
 7     6
 5     3
        
        
BC7, BLB7, BT7, BUB7, LB78, LB789, LBO7700, LL78, LL789, LR78, LR789 All
.   21
 18    15
11     9
 7     6
 5     3
 3      
        
LBNEC7 All
.   22
 19    16
12     10
 8      7
 6      4
 4      3
 3      
2'' C67, LB67 All
.   15
 12    10
  7     3
         
         
T67, TA67, TB67, X67 Thru
.   15
 12    10
  7     3
         
         
Side
.   15
 12     3
         
         
         
L67, LB69, LL67, LR67 All
.   15
 12    10
  7     6
  5     3
         
T68, TB68, X68 Thru
.   15
 12    10
  7     6
  5     4
  3      
Side
.   15
 12    10
  7     6
  5     3
         
BC6, BLB6, BT6, BUB6, C88, E68, LB68, LBD6600, LL68, LL69, LR68, LR69 All
.   15
 12    10
  7     6
  5     4
  3      
T69 Thru
.   15
 12    10
  7     6
  3      
Side
.   15
 12    10
  3      
         
C89 All
.   15
 12    10
  7     6
  3      
1-1/2'' C57, T57, TA57, TB57, X57 All
.    8
  7     3
       
BC5, BLB5, BT5, BUB5, C58, C59, E58, L57, LB58, LB59, LBD5500, LL57, LL58, LL59, LR57, LR58, LR59 All
.    8
  7     6
  4     3
T59 Thru
.    8
  7     6
  4     3
Side
.    8
  7     3
         
T58, TB58, X58 Thru
.    8
  7     6
  4     3
Side
.    8
  7     6
  3      
LB57 All
.    8
  7     6
  3      
1-1/4'' T47, TA47, TB47, X47 Thru
.    6
  3     
   Notes:
Maximum Size of Conductors - Limited to sizes shown in above
table.
Maximum Number of Conductors -
1. Do not exceed quantities shown in above table when installing
No. 4 AWG or larger conductors in a given Crouse-Hinds
conduit body.
2. When installing No. 6 AWG or smaller conductors in conduit
body, the maximum number permitted by N.E.C. Chapter 9,
Tables 3A, 3B and 3C can be used.
Side
.    6
  5     3
C47, LB47, LB49 All
.    6
  3     
BC4, BLB4, BT4, BUB4, C49, C448, E448, L47, LB448, LBD4400, LL47, LL49, LL448, LR47, LR49, LR448, T49, T448, TB49, TB448, X448 All
.    6
  5     3
1'' BC3, BLB3, BT3, BUB3, C37, C38, C39, E37, E39, L37, LB37, LB38, LB39, LB397, LBD3300, LL37, LL38, LL39, LR37, LR38, LR39, T37, T38, T39, T397, TA37, TA38, TB37, TB38, TB39, X37, X38, X39 All
.    3
3/4'' C27, C28, C29, E27, E29, L27, LB27, LB28, LB29, LB297, LBD2200, LL27, LL28, LL29, LR27, LR28, LR29, T27, T28, T29, T297, TA27, TA28, TB27, TB28, TB29, X27, X28, X29 All
.     

                                                                                                                                           
"Side" hub refers to wiring that is pulled through one end hub and out a side hub. "Thru" hub refers to wiring that is pulled through 

 one end hub and out the opposite end hub. "All" hubs refers to wiring pulled through any(side or thru)hub.                                 
National Electrical Code (N.E.C) is a Registered Trademark of the National Fire Protection Association.